VK-ZPDU-V1 series Smart PDU function
3.1 Real-time monitoring function
The monitored total load current, total voltage, total power, total power, power factor, load current of each independent unit can be viewed through the LCD display interface matching button; the contents of the LCD display and closed / off state, temperature / humidity sensor data and operation state, flooding sensor status, smoke sensor state, switch amount output state can be viewed on the web page.
3.2 Control function of the socket unit
3.2.1. When receiving the closing (closing) command, the relay will close after the delay setting time (relay closing delay time);
3.2.2. When receiving the disconnection (switch) command, after the relay set time (relay disconnection delay time), the relay is disconnected;
3.2.3. When receiving the restart command, if the relay is currently closed, after the delay (break delay time), the relay is disconnected, then delay (closing delay time); if the relay is currently disconnected, the delay (break delay time + closed delay time), the relay is closed;
Note: The final result of the restart command is to close the socket.
3.3 Initial state setting
The status of each outlet unit can be selected in three states: closed, disconnected and maintained. (Hold status by default)
Note: The effect of maintaining the current state is after the relay is discharged before power; the disconnected state is after the relay is disconnected; the closed state is after the relay is closed state.